ZW20-12 n'èzí HV agụụ sekit sekit bụ a 3-phase AC 50Hz 12kV mpụga mgba ọkụ akụrụngwa.
♦ Ụzọ ntinye: ogwe osisi;
♦ Ụdị osisi: ogwe aka jikọtara;
♦ Ngwa: n'èzí 12kV substation, ike osisi.
♦ Ụdị ọrụ: akwụkwọ ntuziaka, eletriki, njikwa anya.
Ọnọdụ gburugburu
♦ Elu:
♦ Ọnọdụ ikuku: -40C~ + 40 Celsius C; mgbanwe okpomọkụ kwa ụbọchị
♦ Ọsọ ifufe
♦ Ọkwa ruru unyi: IV;
♦ Ebe nrụnye: Enweghị ọkụ, ihe egwu mgbawa, nnukwu corrosion kemịkalụ ma ọ bụ oké ịma jijiji;
♦ Ike ala ọma jijiji:
Isi Nka na ụzụ Parameters
Mba | Ihe | Nkeji | Uru | |
1 | Egosiri voltaji | kV | 12 | |
2 | Ugboro ike na-anagide voltaji (1min) | (akọrọ) inter-phase, ụwa/ mgbaji; | kV | 42/48 |
(mmiri) inter-phase, ụwa | 34 | |||
3 | Ọkụ ọkụ na-eguzogide voltaji (interphase, ụwa / mgbaji) | kV | 75/85 | |
4 | Enyere ugbu a | A | 630,1250 | |
5 | Ugboro ugboro | Hz | 50 | |
6 | Enyere oke mgbawa sekit dị mkpụmkpụ | ka | 20, 25 | |
7 | Ọnụ ahịa kacha elu akwadoro ugbu a (ọnụọgụ) | ka | 50, 63 | |
8 | Obere oge na-anagide ugbu a | ka | 20, 25 | |
9 | Obere sekit dị mkpụmkpụ na-eme ugbu a | ka | 50, 63 | |
10 | Ogologo oge sekit dị mkpụmkpụ | S | 4 | |
11 | Enyere usoro arụ ọrụ | Oge | O-0.3S-CO-1 80S-CO | |
12 | Enyere akara sekit dị mkpụmkpụ na-agbaji nọmba mmebi ugbu a | Oge | 30 | |
13 | Ndụ mechanical | Oge | 10000 | |
14 | Ogo voltaji arụ ọrụ (nwere ike ịhazi ya) | N'ime | 220 | |
15 | Oge mmeghe | ms | ≤80 | |
16 | Oge mmechi | ms | ≤120 | |
17 | Oge nkwụsị zuru oke | ms | ≤100 | |
18 | Enyere ogo ọcha na-agbaji ugbu a | A | 50 | |
19 | Ọkwa | E2~C2~M2(1000) | ||
20 | Enyere akara sekit dị mkpụmkpụ na-agbaji nọmba mmebi ugbu a | Oge | 30 |
Nha Nhazi na Nrụnye Ozuruọnụ (otu: mm)
Ụzọ ntinye